In short

  • Harmonics come from non-linear loads: drives, UPS units, electronic power supplies, LEDs, welders, furnaces.
  • EN 50160 requires voltage THD ≤ 8% for 95% of the 10-minute values in each week.
  • Current THD at light load is often high but harmless, which is why IEEE 519 uses TDD.
  • Check harmonics before installing or extending power factor correction: capacitors can resonate.

What are harmonics in an electrical installation?

A harmonic is a sinusoidal component of voltage or current at an integer multiple of the supply frequency: on a 50 Hz network the 3rd is at 150 Hz, the 5th at 250 Hz, the 7th at 350 Hz. Harmonics appear because many loads are non-linear: they draw current in pulses even when the supply voltage is a perfect sine wave. By Fourier's theorem, that current is equivalent to the 50 Hz fundamental plus a series of harmonics.

0 10 ms 20 ms Fundamental 50 Hz 5th harmonic 250 Hz (25%) Current drawn
One mains cycle: the double-humped current (blue) is the sum of the fundamental (dashed) and a 5th harmonic at 25% (green). Its THD is 25%.

In a balanced three-phase system the order matters:

  • 5th, 11th, 17th are negative sequence: in motors they create a field that brakes.
  • 7th, 13th, 19th are positive sequence.
  • 3rd, 9th, 15th (multiples of 3, called triplen) are in phase on all three phases: instead of cancelling, they add up in the neutral.

As harmonic currents flow through the impedance of transformers and cables, they cause voltage drops at the same frequencies: Uh = Zh · Ih, where Zh rises roughly with the order h. That is how the current distortion of a few loads becomes voltage distortion for every load on the switchboard. The weaker the supply (small transformer, long cables, standby generator), the higher the voltage THD.

Voltage THD, current THD and TDD: what is the difference?

THD (total harmonic distortion) is the RMS value of all harmonics divided by the fundamental:

THD = √(X2² + X3² + … + XH²) / X1 × 100%

H is the highest order considered: 40 for EN 50160, 50 for IEEE 519. Harmonics add in quadrature: a current with a 5th at 30%, 7th at 15%, 11th at 8% and 13th at 6% has THDi = √(30² + 15² + 8² + 6²) ≈ 35%.

  • THDv (voltage): the quality of the supply seen by every load. The EN 50160 and IEC 61000-2-4 limits apply to this value.
  • THDi (current): how much a load or feeder "pollutes".
  • TDD (total demand distortion, IEEE 519): the harmonic currents divided by the maximum demand current IL rather than by the present fundamental. In practice IL comes from the recorded 15- or 30-minute demand peaks.

At full load THDi and TDD are the same; at light load they are not. Example: a feeder with IL = 400 A. During production, 400 A of fundamental and 140 A of harmonics: THDi = TDD = 35%. At night, 40 A of fundamental and 12 A of harmonics: THDi = 30%, but TDD = 3%.

From the field

A 30-40% THDi recorded at night or at weekends, with the plant almost idle, is rarely a problem: what matters is the amperes of harmonics, not the percentage. The same figure at full load means substantial harmonic currents in transformers and capacitors. Always read THDi together with the current, or use TDD directly, and compare like-for-like time bands: drive manufacturers also point out that THDi rises at part load.

Where do harmonics come from?

Each family of loads has a recognisable spectrum. A p-pulse rectifier produces orders h = k·p ± 1: with 6 pulses the 5th, 7th, 11th and 13th; with 12 pulses the 11th, 13th, 23rd and 25th.

SourceTypical harmonicsNotes
Drives with a 6-pulse rectifier5th, 7th, 11th, 13thTHDi 90-120% with no reactor, 35-45% with a 5% reactor (ABB)
PCs, servers, switch-mode power supplies, LEDs3rd dominantTriplen harmonics add up in the neutral
UPS units and EV chargersDepends on the input stageWith diode or thyristor rectifiers they behave like a drive; with an IGBT rectifier distortion is low
Welders, induction and arc furnacesVariable spectrum, interharmonicsRapidly changing loads, often unbalanced

What damage do harmonics cause?

  • Transformers. Winding eddy-current losses rise with the square of the harmonic current and of the order (IEEE C57.110): the transformer runs hotter than expected and must be derated or chosen with a suitable K-factor (UL 1561).
  • Neutral. Above roughly 33% third harmonic the neutral current exceeds the phase current; with IT loads it reaches about 1.6 times, up to 1.73 in the worst case. IEC 60364-5-52 then sizes the neutral on its own current.
  • Capacitors. Their reactance falls with frequency, so they soak up harmonics. EN 60831-1 rates them for continuous current up to 130% of nominal; the bigger risk is resonance.
  • Circuit breakers. The extra heat causes trips with no obvious overload. Residual current devices trip for different reasons: see the guide on nuisance tripping.
  • Motors. The 5th brakes and heats the rotor; the 5th and 7th together cause torque pulsations at 300 Hz, with vibration.
  • Instruments. Average-responding clamp meters can read up to 40% low on distorted currents: use true-RMS instruments.
  • Electronics and standby generators may become unstable on a distorted voltage.

Which limits apply to voltage and current THD?

There is no single "THD limit": it depends on what is measured, where, and under which standard.

StandardScopeMain values
EN 50160:2022Voltage supplied by public networks, at the LV and MV supply terminalsTHDv ≤ 8% (up to the 40th) for 95% of the 10-minute values in each week, plus limits for individual harmonics
IEC 61000-2-4:2024Industrial networks, at in-plant points of couplingClass 1 (protected supplies, such as laboratory instrumentation); 2a (offices, no industrial power electronics); 2b (light industry and commercial, power electronics alongside ordinary equipment); 2L (the former class 2, for existing installations only); 3 (behind a separation transformer: many converters, welders, frequently started large motors). THDv at 95%: 5% in class 1, 8% in classes 2a, 2b and 2L, 10% in class 3
IEEE 519-2022Point of common coupling (PCC) with the utilityVoltage ≤ 1 kV: 5% per harmonic, 8% THD; 1-69 kV: 3% and 5%. Current: TDD 5-20% depending on Isc/IL
IEC 61000-3-2 and 61000-3-12Individual equipment on public LV networks: up to 16 A per phase (3-2), above 16 A and up to 75 A (3-12)Per-harmonic limits on input current (CE marking)

EN 50160 values for individual harmonic voltages at low voltage (more in the guide to EN 50160):

Odd, not multiples of 3Odd multiples of 3Even
5th: 6% · 7th: 5%3rd: 5%2nd: 2%
11th: 3.5% · 13th: 3%9th: 1.5%4th: 1%
17th: 2% · 19th, 23rd, 25th: 1.5%15th and 21st: see the standard6th-24th: 0.5%

IEEE 519-2022, by contrast, limits the harmonic currents injected by the user, as a percentage of IL, with stricter limits the larger the user is relative to the network (Isc = short-circuit current at the PCC). Systems from 120 V to 69 kV:

Isc/IL2 ≤ h < 1111 ≤ h < 1717 ≤ h < 2323 ≤ h < 3535 ≤ h ≤ 50TDD
< 204.0%2.0%1.5%0.6%0.3%5.0%
20-507.0%3.5%2.5%1.0%0.5%8.0%
50-10010.0%4.5%4.0%1.5%0.7%12.0%
100-100012.0%5.5%5.0%2.0%1.0%15.0%
> 100015.0%7.0%6.0%2.5%1.4%20.0%

Even harmonics up to the 6th are limited to 50% of these values. Compliance is statistical: the weekly 95th percentile of 10-minute values must stay below the limits, while the daily 99th percentile of 3-second values may reach 1.5 times (voltage) or 2 times (current) the limits.

How should harmonics be measured?

A spot reading is not enough: harmonics change with load, shifts and capacitor steps.

  1. A true-RMS instrument with spectrum analysis up to at least the 40th harmonic, preferably the 50th. IEC 61000-4-7 uses 200 ms (10-cycle) windows, which IEC 61000-4-30 aggregates into 3-second and 10-minute values.
  2. Voltage and current together, on all three phases and the neutral: voltage tells you whether there is a problem, current tells you where it comes from.
  3. Main switchboard first, then suspect feeders: drives, UPS units, capacitor banks, IT and lighting circuits.
  4. At least one week, covering shifts, weekends and every duty cycle; if there is a standby generator, also while it is running.
  5. Record the current so that TDD can be calculated, and read percentiles rather than the instantaneous maximum.

Contractual compliance checks call for instruments certified to IEC 61000-4-30 Class A. For diagnosis, continuity is what counts: ALADIN samples voltages and currents at 16 kHz per channel, computes voltage and current THD with harmonic analysis and the 10-minute values for EN 50160 evaluation, with cloud dashboards and automated reports. Left in place for months, it shows the effect of shifts, seasons and changes to the installation.

Caution

Fitting voltage probes and current transformers in a live switchboard is live or near-live electrical work: it must be done by skilled or instructed persons under CEI 11-27 and EN 50110-1.

Harmonics and power factor correction capacitors: why is resonance dangerous?

A capacitor bank and the transformer inductance form a parallel resonant circuit. At resonance a modest harmonic current produces a high harmonic voltage and a large current circulating between capacitors and transformer. The resonant order can be estimated as:

hr ≈ √(Ssc / Qc)

where Ssc is the short-circuit power at the point of installation and Qc the reactive power of the bank in service. Example: a 1000 kVA transformer with 6% impedance gives Ssc ≈ 16.7 MVA (ignoring the upstream network). With 300 kvar in service hr ≈ 7.5; with 500 kvar hr ≈ 5.8. As an automatic bank switches in its steps, the resonance moves from the 7th towards the 5th: exactly the harmonics drives produce. Typical symptoms: capacitors that age early, bank protection that trips, and voltage THD that rises when steps switch in.

The standard answer is a detuned bank: a reactor in series with each step tunes it below the first significant harmonic, at fr = 50 Hz / √p, where p = XL/XC:

  • p = 7%: about 189 Hz (order 3.78), with a good margin below the 5th;
  • p = 5.67%: about 210 Hz (order 4.2), closer to the 5th;
  • p = 14%: about 134 Hz, below the 3rd, where that harmonic is also significant.

Above fr the step is inductive and cannot resonate with the network. The capacitors, however, run at a voltage higher by a factor of 1/(1 − p), about +7.5% with p = 7%, so you cannot simply add reactors to an existing bank. A detuned bank is not designed as a filter: it absorbs only part of the harmonics. Reactive energy costs and penalties are covered in the guide on reactive energy and power factor correction.

How can harmonics be reduced? The options compared

The THDi figures are typical values given by ABB for a drive and depend on network impedance.

OptionTypical THDiWhen it makes senseLimitations
3-5% AC line reactor or DC choke35-45% (with 5%)Baseline for every drive; per ABB, enough when drives are under 30% of transformer capacityNot enough with many large drives
12- or 18-pulse rectifier10-12% / 5-6%Large single drivesFootprint, losses; a 2% voltage unbalance can raise distortion by 50%
Passive tuned filter5-10%Large, steady load with a known spectrumLeading power factor at light load; risk of resonance with other capacitors
Detuned capacitor bank (7%)-Always, when correcting power factor in a plant with harmonicsPrevents resonance but does not filter
Active filter4-7%Many sources, variable load, existing installationsCost; if it fails, the harmonics return
Active front end (AFE) drive3-5%New high-power drives, including regenerative onesCost, slightly more heat in the drive
Dedicated switchboard or transformer for sensitive loads-Disturbances affecting a few loadsDoes not reduce overall distortion
Oversized neutral, K-factor transformer-Many single-phase electronic loadsHandles the heat, not the distortion

When to act: the checklist

After at least a week of measurement, action is worthwhile if:

  1. THDv at the main switchboard approaches or exceeds 8%, or individual harmonics exceed the EN 50160 values or those of the IEC 61000-2-4 class adopted;
  2. TDD at the point of supply exceeds the IEEE 519 limit for your Isc/IL, where a specification requires it;
  3. capacitors fail, bank protection trips, or THDv rises when power factor correction switches in;
  4. neutral current is comparable to phase current, or neutrals and terminals run hot;
  5. the transformer runs hot below rated load, or breakers trip with no overload;
  6. new drives, UPS units, chargers or a larger capacitor bank are planned: measure first.

Action is usually unnecessary if THDi is high only at light load and TDD stays low. A sensible order: measure, trace the sources feeder by feeder, apply low-cost measures at the source, consider active filters or AFE drives, then verify with a new measurement. That is the path of a power quality audit.

Frequently asked questions

What is an acceptable current THD?

There is no universal figure, because THDi depends on load. At the point of supply IEEE 519-2022 sets a TDD of 5% to 20% depending on Isc/IL. What matters most is the effect on voltage THD and on component heating.

Is a multimeter enough to measure harmonics?

No. A true-RMS meter gives the correct total RMS value but not the spectrum; an average-responding one can read up to 40% low. You need a power analyser left in place for at least a week.

Can harmonics cause loads to drop out?

Yes, indirectly: protection tripping on overheating, failed capacitors, drive alarms. First, though, rule out voltage dips and short interruptions, which continuous monitoring records alongside harmonics.

Does an active filter remove all harmonics?

It reduces them upstream of where it is installed, typically to 4-7% THDi. It must be sized on the measured harmonic current, and it does not cure the resonance of a standard capacitor bank.

Sources and standards

Facing a similar problem in your installation?

Tell us what is happening: we help you work out what to measure, where and for how long, before you change anything in the installation.