In short
- Voltage unbalance is the ratio of the negative-sequence to the positive-sequence component: EN 50160 allows 2% for 95% of the 10-minute values in a week.
- In induction motors the currents become 6–10 times more unbalanced than the voltages: above 1% the motor has to be derated.
- Typical causes are poorly distributed single-phase loads, faulty capacitor banks, bad connections and the upstream network.
- IEC, NEMA and IEEE calculate it differently: only compare values obtained with the same method.
What are voltage and current unbalance?
A three-phase system is balanced when the three voltages have the same RMS value and are 120° apart. Under EN 50160 there is unbalance when the RMS values of the line-to-line voltages (fundamental) or the angles between them are not all equal. Currents become unbalanced when the phases carry different loads.
It is measured with symmetrical components: any set of three voltages or currents can be split into three regular sets.
- Positive sequence (U1): rotates in the normal direction; it is the useful voltage.
- Negative sequence (U2): rotates the opposite way; in motors it creates a braking field.
- Zero sequence (U0): three phasors in phase with each other; it exists only in quantities referred to neutral, not in line-to-line voltages. For currents, IN = 3·I0.
The reference factor is u2 = U2/U1 × 100%, computed on the fundamentals. EN 50160 considers only the negative-sequence component, the one that disturbs three-phase equipment; IEC 61000-4-30 (Ed. 4.0, 2025) defines how to measure both voltage and current unbalance.
How do you calculate voltage unbalance? Three methods and an example
The reference method uses magnitudes and angles; the simplified ones only RMS values. The results differ: a value without its method cannot be compared with a limit.
| Method | Formula | Voltages | Notes |
|---|---|---|---|
| IEC 61000-4-30, EN 50160 (u2) | negative / positive sequence × 100 | Fundamentals, magnitude and angle | Basis of European limits and of power quality analysers |
| NEMA MG 1 (LVUR) | maximum deviation from average / average × 100 | Line-to-line | Simple; often slightly lower than u2 |
| IEEE Std 141 (PVUR) | as NEMA | Phase-to-neutral | Includes the zero-sequence component |
Example with line-to-line voltages
Readings at the switchboard: 405 V, 398 V and 391 V.
- NEMA: average 398 V, maximum deviation 7 V, LVUR = 7/398 = 1.76%.
- IEC: line-to-line voltages form a closed triangle, so magnitudes are enough. With β = ΣU4 / (ΣU2)2, u2 = √[(1 − √(3 − 6β)) / (1 + √(3 − 6β))] × 100. Here β = 0.33361 and u2 = 2.03%.
Same voltages, two verdicts: by NEMA the unbalance is below the 2% of EN 50160, by IEC just above it. The β formula, which comes from CIGRÉ and is included in IEEE 1159, needs many digits because β is very close to 1/3: use a spreadsheet.
Phase-to-neutral or line-to-line voltages?
Only phase-to-neutral voltages contain the zero-sequence component. With 6.9 V of zero sequence in phase with L1, the phase voltages become 236.9 / 226.6 / 226.6 V (PVUR ≈ 3%), while the line-to-line voltages all stay at 398.4 V and u2 = 0: a motor without neutral does not notice, single-phase loads do. A large shift of the star point points to an overloaded or badly connected neutral, to be checked at once: a broken neutral leads to overvoltages.
Which limits apply to voltage unbalance?
EN 50160 applies at the point of supply, IEC 61000-2-4 inside the plant network, IEC 60034-1 and IEC 60034-26 to motors.
| Reference | Scope | Values |
|---|---|---|
| EN 50160:2022 | LV and MV point of supply, 10-minute values | u2 ≤ 2% for 95% of the week; at LV up to about 3% where single- and two-phase users prevail |
| IEC 61000-2-4:2024 | In-plant industrial networks | u2 ≤ 2% in classes 1, 2a, 2b and 2L, ≤ 3% in class 3 (Table 1; 95% values over intervals of at least 10 minutes) |
| IEC 60034-1 | Tolerance of three-phase motors | Negative sequence ≤ 1% long term, 1.5% for a few minutes; zero sequence ≤ 1% |
| IEC 60034-26:2026 | Derating of cage induction motors | About 0.95 at 2%, 0.90 at 3%, 0.84 at 4%, 0.75 at 5%; above 5% not recommended (NEMA MG 1 curve similar) |
| Drive manuals | Input unbalance | Typically up to about 3% |
In Italy, ARERA's TIQD (art. 50) makes EN 50160 binding for unbalance too: how to document a non-compliant supply is covered in the EN 50160 guide. Note the gap: a compliant network may sit at 2%, but motors are guaranteed without derating only up to 1%. For the zero-sequence component IEC/TR 61000-3-13 defines no compatibility levels: it is managed through network design and maintenance.
What causes voltage unbalance?
Almost always loads that do not draw the same current on the three phases; less often faults or asymmetries in the network.
- Poorly distributed single-phase loads: lighting, sockets, offices, air conditioners, welders connected between two phases.
- Large single-phase loads at MV and HV: induction furnaces, AC railway traction.
- Faulty capacitor banks: a blown fuse or a degraded capacitor on one phase.
- Transformers: unequal or undersized banks of single-phase units, open-delta connections.
- Connections and faults: a loose terminal on one phase, an undetected earth fault, an open phase upstream.
- Single-phase PV: several inverters on the same phase raise its voltage where the network impedance is high. In Italy, CEI 0-21 sets a power threshold (6–10 kW) above which a generating plant can no longer be connected single-phase.
- Upstream network: unbalance caused by other users reaches the point of supply.
How much unbalance does a single-phase load cause?
A practical estimate: u2 ≈ Sload/Ssc, where Sload is the apparent power of a load connected between two phases and Ssc the short-circuit power at its connection point. With a 1000 kVA transformer with 6% short-circuit voltage (Ssc ≈ 16.7 MVA, ignoring the upstream network), a 200 kVA single-phase furnace causes about 1.2%, which combines with the unbalance already present. Further upstream, where Ssc is higher, the same load unbalances less.
Why does voltage unbalance overheat motors?
Because the negative-sequence component creates a field rotating backwards: for that field the slip is almost 200% and the motor presents a low impedance, as at starting. A small negative-sequence voltage drives large currents, in the rotor at about 100 Hz, where skin effect increases the losses further.
- Currents: according to IEC 60034-26, at normal speed the current unbalance is about 6–10 times the voltage unbalance: 2% can become 12–20%.
- Temperature: an estimate quoted by the US Department of Energy (DOE) puts the increase in temperature rise at 2 × (NEMA unbalance in %)² per cent. At 2.5% that is +12.5%, i.e. 10 K more on a motor with an 80 K rise; every extra 10 K roughly halves insulation life.
- Torque and vibration: locked-rotor, pull-up and breakdown torques fall; a 100 Hz pulsating torque appears, reaching about 25% of rated torque at 5% unbalance, and it can excite torsional vibration.
- Efficiency: that of a 74.6 kW motor tested in the laboratory (DOE data) falls at full load from 94.4% to 93.0% with 2.5% unbalance.
This is why IEC 60034-26 calls for reduced output when the unbalance exceeds 1% for at least the thermal time constant of the motor.
Caution
If a motor's thermal overload trips, do not raise its setting: you lose protection against overload and against running on two phases. Measure the unbalance at the motor terminals first.
What does unbalance do to drives, transformers, cables and the neutral?
Drives and rectifiers
A motor fed by a variable-speed drive receives balanced voltages, because the DC link separates output from input: the problem moves to the rectifier. A small voltage unbalance strongly unbalances the input currents, the rectifier bridge runs hotter and a 100 Hz ripple appears on the DC link, stressing the capacitors. The input current contains non-characteristic harmonics, mainly the 3rd; in 12-pulse rectifiers the cancellation of harmonics gets worse. An input line reactor can balance enough to bring the drive back within the manufacturer's limits.
Transformers
Copper losses grow with the sum of the squared currents: for the same power, an unbalanced load heats more. In delta/star transformers zero-sequence currents circulate in the delta winding and cause additional losses, including in the tank.
Cables and neutral
In 4-wire systems the neutral carries the vector sum of the phase currents. With resistive loads of 150, 100 and 50 A:
- neutral current: √(150² + 100² + 50² − 150·100 − 100·50 − 50·150) ≈ 87 A (loads with the same power factor);
- losses in the phase conductors: +17% compared with 100 A per phase; with a neutral of the same cross-section, +42%;
- with all 300 A on one phase, losses six times higher.
If the neutral stays loaded with balanced phases, the cause is usually triplen harmonics (multiples of 3), which add up in the neutral.
Protection
Unbalanced currents trip thermal overloads, motor protection relays with an unbalance function and three-phase monitoring relays (sequence, phase loss, voltage, unbalance, in some cases also a broken neutral): repeated trips are often the first symptom.
How can you tell whether unbalance comes from the network or the plant?
By measuring voltages and currents together at the point of supply for at least a week and comparing the voltage unbalance with the unbalance of the currents drawn.
- At the main switchboard record u2 (10-minute values, 95th percentile, maxima), phase and neutral currents and current unbalance.
- Compare the trends: if u2 stays similar with the plant stopped (nights, holidays), it comes from the network; if it follows your currents or certain machines, it is internal. The S/Ssc estimate tells you whether a load is enough to explain it.
- Go down to the feeders: phase currents show where single-phase loads are concentrated.
- Check power factor correction: with the steps switched in, the three currents should be almost equal; a lower one means a blown fuse or a degraded capacitor.
- Thermal imaging of switchboards: a loose terminal heats up on one phase only.
- At the terminals of critical motors: that is where the IEC 60034-1 limits apply.
ALADIN computes voltage unbalance as the ratio of the negative- to the positive-sequence component of the fundamental line-to-line voltages, with the IEC 61000-4-30 method (zero sequence excluded), and current unbalance with the same method, with 10-minute values for EN 50160 assessment, cloud dashboards and automated reports. For several measuring points there is the power quality audit; the campaign is set up as described in the power quality analysis guide.
From the field
Current unbalance in per cent must be read together with the amps. With the plant almost idle, a few single-phase loads give very high but harmless percentages; at full load the same value means losses, a loaded neutral and more voltage unbalance. Balance on currents measured at peak times, not on nameplate data.
Caution
Connecting instruments in a live switchboard and moving circuits between phases is electrical work, reserved for skilled or instructed persons under CEI 11-27 and EN 50110-1.
How do you correct voltage unbalance?
First balance the loads and repair faults, which is cheap; balancing devices are for large single-phase loads or loads that cannot be moved.
| Measure | When | Limits |
|---|---|---|
| Redistribute single-phase loads on measured currents | Unbalance from LV loads | Loads change: measure again |
| Repair the capacitor bank, tighten connections | Different currents or temperatures on one phase | Check harmonics and resonance too |
| Connect large single-phase loads where Ssc is higher, via a dedicated transformer, or choose three-phase versions | Furnaces, welders | Cost of the works |
| Steinmetz circuit or Scott transformer | One large, steady single-phase load | Perfect balance only at the design load |
| Active filter with load-balancing function | Many variable loads, overloaded neutral | Cost; sized on the current to compensate |
| SVC or STATCOM | Railway traction, furnaces, large users | High cost |
| Motors: derate, feed via a drive, protection with an unbalance function | Network unbalance that cannot be removed | The drive moves the problem to its rectifier |
| Report to the distributor | u2 above 2% at the point of supply even with the plant stopped | At least one week of measurements needed |
In an example published by ABB, an active filter brought currents of 49, 5 and 5 A to about 19.5 A per phase and the neutral current from 44 to 3.5 A.
What does voltage unbalance cost?
More than it seems, because the costs are scattered.
- Motor energy: in the DOE example the 74.6 kW motor, at full load for 8,000 hours a year, uses 9,517 kWh more with 2.5% unbalance: at a hypothetical €0.15/kWh, about €1,400 a year for a single motor.
- Cables: in the 150/100/50 A example losses rise by 17–42%.
- Service life: 10 K more roughly halves insulation life, bringing rewinds and replacements forward.
- Derating: at 3% unbalance the motor should be loaded to no more than 90% of its rated output.
How to add them to downtime and other disturbances is explained in the guide on the cost of power quality.
Frequently asked questions
What is an acceptable voltage unbalance?
For motors up to 1%, the value IEC 60034-1 guarantees without derating; at the point of supply EN 50160 allows 2% for 95% of the 10-minute values. Above 5% motors should not be run.
Is there a limit for current unbalance?
Not a general one. It is judged in amps: neutral current, the most loaded phase against the cable rating, and the effect on voltage unbalance.
Why do different instruments show different unbalance?
Because they use different methods: NEMA on line-to-line voltages, IEEE on phase-to-neutral voltages, IEC on symmetrical components. For EN 50160 you need u2 according to IEC 61000-4-30.
Why is there neutral current when the phases are balanced?
Almost always because of triplen harmonics from electronic power supplies and LEDs, which add up in the neutral: see the guide on harmonics.
Does a variable-speed drive protect the motor from unbalance?
Yes, the motor receives balanced voltages, but the unbalance stresses the drive's rectifier and capacitors, which manufacturers typically accept up to about 3%.
Sources and standards
- EN 50160:2022 + A1:2025; European Copper Institute, Application Note Cu0147 (2013).
- IEC 61000-4-30:2025; IEC 61000-2-4:2024; IEC/TR 61000-3-13:2008.
- IEC 60034-1:2026 (clause 7.2.1.1, checked against the 2010 edition); IEC 60034-26:2026; NEMA MG 1.
- S. Bogarra et al., New Smart Sensor for Voltage Unbalance Measurements, Sensors, 2022 (IEC, CIGRÉ, NEMA and IEEE definitions).
- US DOE, Eliminate Voltage Unbalance, Motor Systems Tip Sheet #7 (2012).
- ABB, Three-Phase Voltage Imbalances (2022); Nidec, Unbalanced Voltage.
- M.O. Roux et al., Low-order Non-characteristic Harmonics of Rectifier Loads, IPST 2007.
- J. Driesen, T. Van Craenenbroeck, Introduction to Unbalance, Power Quality Application Guide 5.1.3, European Copper Institute, 2002.
- ABB Review 4/2010, Actively improving quality; Hitachi Energy, Evron, France; ABB, CM-MPS data sheet.
- ARERA, TIQD (resolution 617/2023/R/eel), art. 50; CEI 0-21 and CEI FAQ; CEI 11-27; EN 50110-1.