In short

  • Three families: sustained overvoltages (hours), temporary 50 Hz overvoltages (10 ms – 1 min) and transients (microseconds – milliseconds).
  • At low voltage the 10-minute values must not exceed 253 V; above that, the usual causes are light load, the transformer tap, local generation and over-correction of power factor.
  • A broken neutral can push single-phase equipment towards 400 V.
  • Lightning and switching produce impulses of thousands of volts, limited by coordinated Type 1, 2 and 3 SPDs with short connections.
  • An RMS-based recorder sees the first two families, not transients.

What types of overvoltage occur in electrical installations?

Three, which differ in duration, origin and remedy. Mixing them up is the most common mistake: a surge protective device does nothing against a voltage that stays high for hours, and an overvoltage relay will not stop a lightning surge. EN 50160 also calls temporary overvoltages "voltage swells".

FamilyThreshold or amplitudeDurationTypical causesMeasured with
Sustainedabove +10% on 10-minute values; at LV above 253 Vminutes – hourslight load, transformer tap, generation, capacitors10-minute mean values
Temporary, power frequencyabove 110% of the reference voltage10 ms – 1 minearth faults, load shedding, broken neutralevents on RMS values
Transientimpulses or oscillations up to thousands of voltsunder 1 µs – a few mslightning, switching of breakers, fuses and capacitorstransient capture

The overview of all disturbances is in the guide to power quality and electrical disturbances.

Why does the voltage stay too high for hours?

Because the voltage at the point of supply is the substation voltage minus the drops along lines and transformers: when those drops shrink or reverse, the voltage rises and stays up. On 230 V low-voltage supplies the 10-minute mean values must not exceed 253 V (440 V between phases on 400 V systems), and in Italy ARERA allows no statistical margin: see the guide to EN 50160.

  • Light load: at night and at weekends the voltage drops shrink and the voltage moves towards its no-load value.
  • MV/LV transformer tap: for MV customers, the off-load tap (usually ±2×2.5%) chosen for full load can push the LV side too high at light load; each step is worth about 2.5%.
  • Generation on the feeder: PV exporting to the grid reverses the power flow and raises the voltage in sunny hours.
  • Over-correction: capacitors left in at light load raise the voltage by about du% ≈ uk% × Qc/Sn; with fixed capacitors equal to 20% of the transformer rating and uk 6%, +1.2% at no load. See reactive energy and power factor correction.

The effects: shorter insulation life in motors, contactor coils and capacitors; generators dropping off, because the CEI 0-21 interface protection disconnects them when the 10-minute moving average exceeds 110% of nominal voltage and, within a few tenths of a second, above 115% (CEI 0-21 Table 13: 59.S1 works on the 10-minute moving average recalculated at least every 3 s; 59.S2 trips in 0.2 s). These costs belong in the accounts: see what power quality problems cost. The distributor, however, answers only for the regulated limits: in decision 325/2026/E/eel ARERA rejected the complaint of a producer whose inverter curtailed output at around 249 V, because the 10-minute values had not exceeded 247.42 V.

How to check and what to do

  1. Measure 10-minute values for at least a week, nights and weekends included, at the point of supply and on the main feeders (see power quality analysis). Above 253 V at the point of supply even with the plant stopped: ask the distributor for a voltage check.
  2. MV customers: review the transformer tap, which may only be changed with the transformer de-energised.
  3. Power factor correction: automatic controller, and capacitors switched out when the plant is idle.
  4. PV: compare the voltage at the inverter and at the meter; an undersized cable adds a voltage rise that is entirely yours.

What are temporary overvoltages and where do they come from?

They are rises of the RMS voltage above 110% of the reference voltage, lasting from 10 ms to 1 minute, between phases or to earth. EN 50160 sets no maximum number of events; it classifies them by maximum voltage and duration:

Maximum voltage u10–500 ms0.5–5 s5–60 s
u ≥ 120%S1S2S3
120% > u ≥ 110%T1T2T3
  • Earth faults on the MV network: on isolated or compensated neutral networks a single-phase earth fault raises the voltage to earth of the healthy phases for as long as the fault lasts; with an isolated neutral and a solid fault, up to the line-to-line voltage.
  • Transfer to LV: an MV fault in the substation stresses the insulation of LV equipment. On a TT system CEI 64-8 (clause 442.3) only allows the LV neutral to share the substation earth if the total earth voltage stays within 250 V when the fault is cleared in more than 5 s, or 1200 V within 5 s. At 230 V, LV equipment therefore sees up to about 480 V or 1430 V to earth, the same U0 + 250 V and U0 + 1200 V as IEC 60364-4-44. According to the e-distribuzione–Confindustria guide, at LV they generally stay below 1.5 kV thanks to effective neutral earthing.
  • Line-to-neutral short circuit at LV: up to 1.45 U0 (about 333 V) for no more than 5 s.
  • Load shedding: disconnecting a large load removes its voltage drop at once.
  • Ferroresonance on MV: high, distorted overvoltages, usually involving inductive voltage transformers.

Single-phase equipment and power supplies suffer first; varistor SPDs, built for short impulses, also overheat if the overvoltage lasts for seconds.

Why does a broken neutral destroy equipment?

Because without the neutral, single-phase loads on different phases end up in series across the 400 V line-to-line voltage, which divides according to their impedances: the least loaded phase gets the highest voltage, up to almost √3 U0, about 400 V.

Example with resistive loads: 2 kW on L1, 0.5 kW on L2, nothing on L3. At 230 V the resistances are 26.45 Ω and 105.8 Ω; with the neutral broken they are in series across 400 V and about 3 A flows: the large load falls to 80 V, the small one rises to 320 V.

  • Causes: loose or poorly made terminations, damaged conductors, neglected maintenance.
  • Signature: phase-to-neutral voltages drift apart while line-to-line voltages stay normal; the shift grows with load unbalance.
  • Protection: tightening and periodic checks; relays monitoring phase and neutral voltages at switchboard incomers, opening the breaker through a shunt trip (with perfectly balanced loads they may not notice); for circuits up to 63 A, POP devices (EN IEC 63052).

From the field

An overvoltage on one phase and a drop on another at the same instant, with steady line-to-line voltages, point to a shifted neutral, not a grid overvoltage. Check the instrument's neutral connection first: a loose or floating one produces the same picture. If the instrument is fine, the loose neutral is in the installation and needs checking at once.

Where do transient overvoltages come from?

From lightning and switching. They are impulsive or oscillatory overvoltages, usually heavily damped, lasting a few milliseconds or less, with rise times from under a microsecond to a few milliseconds. A direct strike hits the building or its supply line; an indirect one lands nearby and induces voltages in the circuits. Typical LV amplitudes according to the e-distribuzione–Confindustria guide:

OriginDurationTypical amplitude
Switching short cables and busbars, interrupting inductive currentsunder 1 µsup to 1–2 kV
Lightning on the MV network transferred through the transformer1–100 µsup to 4–6 kV
Direct or indirect strikes on LV lines1–100 µsup to a few tens of kV
Fuse operationover 100 µsup to 1–2 kV
Capacitor bank switchingover 100 µsup to 2–3 times the nominal peak

Magnification at capacitors. When an MV capacitor bank is energised upstream, the oscillation can excite the resonance between the MV/LV transformer and the plant's power factor correction capacitors, the same resonance that amplifies harmonics. A technical paper from S&C Electric gives frequencies of 300–800 Hz and, without switching control, overvoltages of up to 3.2 per unit at remote capacitors. The typical victim is a drive without an AC line or DC bus choke, which trips on DC bus overvoltage.

Effects. Punctured insulation in motors, cables and machines; failed control and power electronics; upsets on PLCs and data lines; RCDs that trip (immunity and SPD position are covered in the guide to nuisance tripping).

How much impulse voltage must equipment withstand?

It depends on where it sits in the installation. IEC 60664-1 and CEI 64-8 assign equipment to four overvoltage categories; on 230/400 V systems the required rated impulse withstand voltage Uw (1.2/50 µs wave) is:

CategoryUwExamples
IV6 kVorigin of the installation: meters, protective devices upstream of the board
III4 kVfixed installation: switchboards, switches, permanently connected machinery
II2.5 kVcurrent-using equipment, portable tools
I1.5 kVsensitive equipment such as electronics

The SPD voltage protection level Up between live conductors and PE must not exceed the Uw of the equipment to be protected: on 230/400 V TN and TT systems the reference is category II, 2.5 kV. The same standard (CEI 64-8, clause 534.4.4.2) recommends staying within 80%, 2.0 kV, to leave a margin for the connections.

Type 1, 2 and 3 SPDs: which one is needed and where does it go?

CEI 64-8 (section 443) requires protection against transient overvoltages where the consequences affect human life, public services and cultural heritage, commercial or industrial activity, or large numbers of people; in other cases a simplified risk level (CRL) is calculated, and if it is not, protection must be provided anyway. A plant designed to the current standard therefore needs SPDs; the lightning risk of the structure is assessed with CEI EN IEC 62305-2:2025.

TypeTestWhere and when
Type 1impulse current Iimp, 10/350 µs waveorigin of the installation (in MV-supplied plants, the main LV board), mandatory if the building has a lightning protection system (LPS); some manufacturers also advise it with an overhead supply line. Without a risk assessment to CEI EN 62305-2, at least 12.5 kA per pole (more between neutral and PE in the CT2 connection)
Type 2nominal discharge current In, 8/20 µs waveorigin in all other cases, and sub-distribution boards; at the origin In at least 5 kA per pole (more between neutral and PE in the CT2 connection)
Type 3combination wave 1.2/50 µs – 8/20 µsclose to sensitive equipment, only downstream of a Type 1 or 2

Test requirements are in IEC 61643-11:2025, read together with IEC 61643-01:2024. The installation rules that make the difference:

  1. Short leads: from the live conductor to the SPD and from the SPD to PE, 0.5 m in total. Each metre is about 1 µH and, at 10 kA with an 8/20 µs wave, adds about 1 kV to the voltage seen by the equipment.
  2. Distance: beyond about 10 m of cable between SPD and equipment, a further SPD is needed close to the equipment.
  3. Coordination: Types 2 and 3 only downstream of the SPD at the origin, energy-coordinated and with the overcurrent protection specified by the manufacturer.
  4. Other lines: where SPDs are needed on the power supply, the standard recommends protecting telephone and data lines too.
  5. Status: an overloaded or aged varistor SPD disconnects itself from the supply; check the indicator after storms.

Caution

Installing or replacing SPDs, changing a transformer tap and connecting instruments in switchboards is electrical work reserved for skilled or instructed persons under CEI 11-27 and EN 50110-1. SPD selection is the designer's job; instruments must have a measurement category suited to the connection point.

How are overvoltages measured and which instrument is needed?

  • Sustained: 10-minute RMS mean values for at least a week, compared with 253 V and with EN 50160.
  • Temporary: with the IEC 61000-4-30 method, the same used for voltage dips, the RMS value is computed over one cycle (20 ms) and refreshed every half cycle; the event starts when at least one phase exceeds the threshold, 110% for EN 50160, and ends when all phases fall back below the threshold minus a small hysteresis. Record both phase-to-neutral and line-to-line voltages to spot neutral problems.
  • Transient: an RMS value over 20 ms flattens a microsecond impulse. A transient capture function is needed: the Fluke 1777, for example, samples transients at 1 or 20 MS/s up to ±8 kV peak, against 80 kS/s for its ordinary measurements.

An analyser that samples at 16 kHz and detects events on half-cycle RMS values, such as ALADIN, records temporary overvoltages with time, duration and maximum value, plus the current drawn just before, which helps to recognise load shedding, and the 10-minute values for sustained ones. It does not record microsecond impulses: a storm with no RMS events does not rule out a transient.

Equipment burnt out after a thunderstorm: what should you do?

Document before replacing. In commercial and industrial settings the indirect damage, such as lost production and lost data, often exceeds the value of the equipment, and insurers or any dispute will ask for evidence of the event.

  1. Note date, time, the equipment and the ports that failed: damage on both power and data connections points to a potential difference between the two networks.
  2. Check SPD indicators and their back-up protection: if they operated, the surge got in.
  3. Collect recorded voltage events, interruptions reported by the distributor and lightning location data.
  4. Tell them apart: only single-phase equipment failing, in several places, suggests the neutral; power supplies failing at night or at weekends, a sustained overvoltage; SPDs operated after a storm, transients.

To estimate the value of the damage avoided see the cost of power quality; to find the cause with measurements at several points there is the Power Quality audit.

Frequently asked questions

What is the maximum allowed low voltage?

253 V on 10-minute mean values at 230 V and 440 V between phases at 400 V, with no statistical margin in Italy. Short events above 110% are temporary overvoltages.

Does a surge protective device protect against a broken neutral?

No: it limits microsecond impulses, and a 50 Hz overvoltage lasting a few seconds can overheat it and disconnect it. A broken neutral calls for sound connections and monitoring relays.

Why does the PV inverter disconnect on overvoltage?

The CEI 0-21 interface protection trips above 110% of nominal voltage as a 10-minute average and above 115% within 0.2 s (59.S2). If the voltage at the meter stays below 253 V, look for the problem in the plant's own connection.

Does a power analyser record lightning?

Only if it has transient capture, with sampling in the megahertz range; RMS values show temporary overvoltages, not impulses.

Sources and standards